To change an access code:
1.
Enter the installer code. The panel will automatically go to the main menu.
2.
Select 6 for Network Programming Menu.
3.
Select 5 for Access Codes.
Display reads:
4.
Select the access code you wish to edit by pressing the up or down arrow key.
5.
Then press ENTER.
Profile Edit Menu
From the Profile Edit Menu you can change the users name, access code, and the panel functions that the user will have access to with
their code.
NOTE: Profile 1 (Fire Fighter's Key) the user name and access code can not be edited. Profile 2 (Installer) the user name and panel functions
can not be edited. Profile 3 (Multi-Site Installer) is defaulted with the Multi-Site access option, but the entire profile can be edited.

Edit Name

6.
See Appendix B for a list of available characters and their numeric designators.
7.
Then press ENTER to finish.

Edit Access Code

8.
Enter new access code (minimum of 4 digits, maximum of 7 digit).
9.
Press ENTER.
10. Enter code again. Press ENTER.

Panel Functions

11. Press the up or down arrow key to move through the list of available functions.
12. Then press right arrow to move to Y (yes) or N (no) selection column.
13. Press the up or down arrow key to select Y or N.
14. Press ENTER.
15. Repeat steps 12 through 15 until user profile is complete.
6.2.6 Communicator Options
Communicator options provides the configuration for reporting events to a central station.
1.
From the main menu.
2.
Select 6 for Network Programming.
3.
Press 6 to enter Communicator Options menu.

Communicator Assignments

Each panel on the 6820/EVS communication link system specifies which communicator is used for reporting. The communication link
capability of the linked system allows all panels to use the same communicator providing an economical solution for reducing the num-
ber of paths required for reporting purposes. A communicator is specified by panel number. The communication link will be used to
report events according to the communicator report table.

Communicator Miscellaneous

When using the SIA reporting format, the communicator sends information according to the SIA Reporting Type. The selections for this
option are:
1.
pi modifier (default)
2.
Panel ID*
NOTE: *Only SIA sends the panel ID when reporting.

Receiver Configuration

The 6820/EVS system can report events to as many as 68 receivers. See Appendix C for panel/receiver relationship numbers. Each
receiver is assigned a phone number and reporting format. Phone numbers can be up to forty digits long.
1.
From the main menu.
2.
Select 6 for Network Programming.
3.
Press 6 to enter Communicator Options menu.
4.
Select 3 for Receiver Configuration.
5.
Select Panel to Program and press ENTER.
6.
Enter the receiver number that you want to report to. The receiver numbers available will correspond with what panel number you
entered. Receiver numbers are populated based on panel number and audited to allow only the 4 appropriate receivers. See
Appendix D for receiver number
80
Select Profile 01
Fire Fighter's Key
6820 / 6820EVS Manual P/N LS10144-001SK-E:C 09/28/2017