If both the fire alarm and EVS are active and the active EVS event is programmed for higher priority than fire alarm; the user must
also have gained EVS control.
In this case a fire page is NOT allowed at all and the LOC must gain EVS control in order to do any live voice.
11.7.4 Emergency Page
An emergency page can occur when:
1.
Only the emergency system is active and the user has gained EVS Control.
2.
Only fire alarm is active, custom EVS is higher priority than fire alarm and the user has gained EVS Control.
This will trigger the EVS system and enable mapping for 'Custom EVS' and 'General EVS'.
11.7.5 Paging
If there are no active emergency or fire system events, the microphone at an LOC can be used for paging by following these steps:
1.
Remove the microphone from its cradle.
2.
Press the push-to-talk button on the microphone.
3.
Use the Select Keys on the LOC to toggle the output areas to page to with the microphone (illuminates the green LEDs).
NOTE: The Ready to Talk LED will illuminate after an output area has been activated.
4.
Speak into the microphone.
5.
Release PTT button when finished.
156
Ready to Talk LED
6820 / 6820EVS Manual P/N LS10144-001SK-E:C 09/28/2017