Honeywell Silent Knight SK318PT Installation And Operation Manual page 98

Addressable fire system, emergency voice system
Table of Contents

Advertisement

To address:
1.
Connect a detector base temporarily to the programming terminals as shown in Figure 7.7. (You can use the same base for each
detector.)
2.
Enter the Installer code. The panel will automatically go to the main menu.
3.
Select 2 for Point Functions.
4.
Select 3 for Set SLC Device Address.
5.
Select "Yes" by pressing the up arrow, then press ENTER. (The panel will go into trouble at this point. You can use the SILENCE
key to stop the PZT. The trouble will clear automatically when the panel re-boots when you finish programming.)
6.
When the wait message clears, the following options display:
1- for Read Address. Use to read (or check) a single detector's address.
2- for Write Address. Use to program a single detector's address.
3- for Seq. Programming. Use to program more than one detector in sequential order.
7.
If you are changing addresses, write the programmed address on the back of the device.
8.
To exit press left arrow until fully exited.
94
Figure 7.7 Temporary Connection of Detector Base to Panel for Addressing
6820 / 6820EVS Manual P/N LS10144-001SK-E:C 09/28/2017