4: Maximum Battery Standby Load - Honeywell Silent Knight SK318PT Installation And Operation Manual

Addressable fire system, emergency voice system
Table of Contents

Advertisement

5.
Total does not include isolator devices or accessory bases.
3.7.4 Maximum Battery Standby Load
Tables 3.4 and Table 3.5 show the standby load calculations for the 6820 / 6820EVS based on 24 and 90 hours of standby. The standby
load calculations of line D in the Current Draw Calculation Worksheet must be less than the number shown in Table 3.4 and Table 3.5 for
the selected battery size, standby hour and alarm time. The numbers below have a built in 20% derating factor for the battery amp-hour
capacity.
WARNING:
!
Honeywell Silent Knight does not support the use of batteries smaller than those listed in Table 3.4 and Table 3.5. If you use a battery too small
for the installation, the system could overload the battery resulting in the installation having less than the required 24 hours standby power. Use
Table 3.4 and Table 3.5 to calculate the correct battery amp hour rating needed for your installation. It is recommended that you replace
batteries every five years
*For FM Installation only
6820 / 6820EVS Manual P/N LS10144-001SK-E:C 09/28/2017
Rechargeable
24 hr Standby,
Battery Size
5 mins. Alarm
17AH
535 mA
18AH
569 mA
24AH
769 mA
33AH
1.07A
35AH
1.14A
40AH
1.30A
55AH
1.80A
Table 3.4 Maximum Battery Standby Loads for 24 hours Standby
Rechargeable
90 hr Standby,
Battery Size
5 min alarm
33 AH
N/A
40 AH
347 mA
55 AH
480 mA
Table 3.5 Maximum Battery Standby Loads for 90 hour Standby*
24 hr Standby,
24 hr Standby,
15 min alarm
20 min alarm
473 mA
442 mA
506 mA
475 mA
706 mA
675 mA
1.01A
975 mA
1.07A
1.24A
1.74A
90 hr Standby,
90 hr Standby,
15 min alarm
20 min alarm
N/A
331 mA
322 mA
464 mA
456 mA
1.04A
1.21A
1.71A
N/A
27

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Silent knight 6820Silent knight 6820evs

Table of Contents