1: Edit Zone; Edit Zone Name; Edit Zone Properties - Honeywell Silent Knight SK318PT Installation And Operation Manual

Addressable fire system, emergency voice system
Table of Contents

Advertisement

9.3.1 Edit Zone
Features that can be edited through the edit zone option are zone name, zone properties (which includes zone type and detector sensitiv-
ity), and zone accessory options.
To edit a zone, follow these steps:
1.
Enter the installer code. The panel will automatically go the main menu.
2.
Select 7 for Program Menu.
3.
Press 2 to enter zone menu.
4.
Press 1 to edit a zone.
5.
Enter the zone number, then press ENTER.

Edit Zone Name

6.
Press 1 to edit the selected zone name.
You can use words to display a descriptive name for a zone.
NOTE: See Appendix B for editing names.

Edit Zone Properties

Zone properties consist of alarm delay characteristics, heat detector sensitivity.
1.
Do steps 1 through 5 of Section 9.3.1.
2.
Press 2 to edit the properties of the selected zone.
Alarm Delay Characteristics
The programmed zone type is provided for user reference only. To modify the zone type, use the HFSS Honeywell Fire Software Suite.
Table 9.1 list the detector characteristics and a description of each.
Type of Delay
1-Count
2-Count
Alarm Verification
116
Figure 9.2 Editing Zone Properties
One Count (No Delay). When this option is enabled, an alarm occurs immediately when a single device
of any of the following types goes into alarm: detector, manual pull, water flow, Zone Aux1 or Zone
Aux2. This is considered the most typical operation and is the default for all zones.
When this type of alarm delay is used, two or more detectors within the zone must go into alarm in
order for the zone to report an alarm. Switches of type manual pull, Detector Switch, water flow, Zone
Aux1 and Zone Aux2 are an exception; they will cause an alarm when only one switch is in alarm.
When a single detector is in alarm in a 2-Count zone, the system enters a prealarm condition. In a
prealarm condition, the touchpad PZT beeps and the annunciator display indicates that a prealarm has
occurred. If the zone has been mapped to an output group for the prealarm event, the output group will
activate. The prealarm will not be reported to the central station.
When two count is used, detector spacing shall be cut in half. You should, not use the alarm verification
feature, and no delay shall be used.
Alarm verification is an optional false alarm prevention feature that verifies an alarm condition by
resetting the smoke detector. If the alarm condition still exists by the time the reset cycle has
completed, the detector will go into alarm. If the detector is no longer in alarm, no report will go to the
central station. The alarm verification sequence is ignored if the zone is already in alarm.
Table 9.1 Alarm Detector Characteristics
Description
6820 / 6820EVS Manual P/N LS10144-001SK-E:C 09/28/2017

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Silent knight 6820Silent knight 6820evs

Table of Contents