Type of Delay
P.A.S.- Positive Alarm
Sequence
Single Interlock
Double Interlock
Note: SK-Fire-CO and other CO detectors can only be installed in a 1 count zone.
Heat Temperature Setting
Use this feature to set the temperature at which high temperature detectors will respond.All detectors in the zone will respond in the same
way.The range for SK-Heat-HT heat detector is from 135°F to 190°F and the range for SD505-HEAT is 135°to 150°F.
The high temperature SK heat detectors are absolute temperature devices. This means that they respond to an alarm immediately if the
temperature in the zone goes above the programmed temperature.
3.
Enter the temperature at which the heat detector will respond, or use the up or down arrow key to scroll through the range, or enter
directly from the number keys on the annunciator, then press ENTER.
4.
Use the up or down arrow key to scroll through the range or enter directly from the number keys on the annunciator, then press
ENTER.

Zone Accessory Options

1.
Do steps 1 through 5 of Section 9.3.1.
2.
Press 3 to edit the Zone's Accessory options.
Single or Multi-Station cadence pattern (choose from Patterns 00 to 02, 23 if using SK. Choose from 00-16, 23 if using SD devices). See
Appendix D.
CO Single and Multistation Cadence (choose from Cadence Patterns 00 to 02, 23 for SK devices).
NOTE: The B200S Sounder base provides the recommended CO cadence pattern.
Local Zone (choose Y or N, for Yes or No).
NOTE: If the SLC protocol is changed from SD to SK series and the cadence is no longer valid for SK, the zone cadence will be set to constant
on.
9.3.2 View Zone Points
To view the points in a zone, follow these steps:
1.
Enter the installer code. The panel will automatically go to the main menu.
2.
Select 7 for Panel Programming.
3.
Press 2 to enter zone menu.
4.
Press 2 to view zone points.
5.
Enter the number of the zone you wish to view, then press ENTER.
6820 / 6820EVS Manual P/N LS10144-001SK-E:C 09/28/2017
This option is intended to be used with an acknowledge switch. An alarm is delayed for 15 seconds,
giving on-site personnel a chance to investigate the alarm. If the acknowledge switch is not activated
within 15 seconds, an alarm occurs automatically.
If this option is enabled for a zone, the zone will respond to an alarm condition as follows:
• The zone will not go into alarm for 15 seconds to allow an on-site operator to activate the
acknowledge switch.
• If the operator does not press the acknowledge switch within 15 seconds, the zone will go into
alarm.
• If the operator presses the acknowledge switch within 15 seconds, a 180-second time-frame will
begin counting down. This time-frame allows the operator to investigate the cause of the alarm.
If the operator performs a reset within 180 seconds, the alarm will not occur. If the operator does
not perform a reset within 180 seconds, an alarm will occur automatically.
• The P.A.S. feature will be overridden if another alarm occurs.
See Section 10.7.1 for single interlock releasing operation.
See Section 10.7.2 for double interlock releasing operation.
Table 9.1 Alarm Detector Characteristics
Figure 9.3 View Zone Points Screen
Description
Zone Number
Zone Name
117