4.
Press the up or down arrows to select the desired module. Refer to Section 8.5 for available choices. Then press ENTER.
Select an output
group for this
Zone/Group
Select a name
for the Point
5.
Enter the point number, then press ENTER.
6.
Press the up or down arrows to select the type (notification or unused). Press ENTER.
7.
Press the up or down arrows to select the desired group.
8.
Press ENTER.
9.
Edit point name. See Section 9.6. Or, press the right arrow to skip module name edit.
10. Repeat Steps 1 through 9 for all points.
9.5.5 Point Programming For EVS-VCM and EVS-RVM Modules
To program EVS-VCM and EVS-RVM module points:
1.
Enter the installer code.
2.
Select 7 for Program Menu.
3.
Press 4 to enter point menu.
4.
Press the up or down arrows to select the desired module. Refer to Section 8.5 for available choices. Press ENTER.
5.
Enter the point number. Press ENTER.
6.
Press the up or down arrows to select the type (Switch or unused). Press ENTER.
7.
Press the up or down arrows to select the function. Press ENTER.
8.
Use the up or down arrows to modify and remaining options and use ENTER to move to the next field.
9.
Edit module name. See the Section Naming Modules. or, Press the right arrow to skip module name edit.
126
Select NOTIF or UNSED
Figure 9.5 Programming Points as Outputs for the 5880 Module
Select Switch or Unused
Figure 9.6 Programming Points as Inputs for the 5880 Module
Select Function
6820 / 6820EVS Manual P/N LS10144-001SK-E:C 09/28/2017