Honeywell Silent Knight SK318PT Installation And Operation Manual page 30

Addressable fire system, emergency voice system
Table of Contents

Advertisement

Device
EVS-50W or EVS-125W Audio Amplifier
with/without EVS-CE4
EVS-INT50W Internal Amplifier
EVS-VCM Voice Control Module
EVS-SW24 Switch Expander
EVS-LOC Remote Command Unit
(includes 6860, RVM & SW-24)
EVS-100W 100W Amplifier
EVS-100WBU backup daughter card
A
Total System Current
Network Cards
SK-NIC Network Interface Card
SK-FML Fiber Optic Multi Mode
SK-FSL Fiber Optic Single Mode
3
Auxiliary Devices
IPDACT-2 IP Communicator
IPDACT-2UD IP Communicator
CELL-MOD/CELL-CAB-SK
B
Auxiliary Devices Current
Notification Appliance Circuits
5495/5499 Power Supply
C
Notification Appliances Current
D
Total current ratings of all devices in system (line A + line B + C)
E
Total current ratings converted to amperes (line D x .001):
F
Number of standby hours:
G
Multiply lines E and F.
H
Alarm sounding period in hours. (For example, 5 minutes = .0833 hours)
I
Multiply lines E and H.
4
J
Add lines G and I.
Multiply by the Derating Factor
1.
The FACP can only support 5 devices w/LED's on. This current draw has been added to the panels alarm current.
2.
If using 24 VDC aux power only. No standby or alarm current for battery calculation if using 24 VAC, 120 VAC or 240 VAC.
3.
If using door holders, you do not need to consider door holder current for alarm/battery standby, because power is removed during
that time. However, during normal operation, door holders draw current and must be included in the 6.0A total current that can be
drawn from the panel.
4.
Use next size battery with capacity greater than required.
26
# of Devices
(4 max.)
(4 max.)
(1max.)
(5 max.)
(4 max.)
(4 max.)
(4 max.)
(1 Max.)
(1 Max.)
(1 Max.)
Refer to devices manual for current rating.
(1 max.)
(1 max.)
Refer to device manual for current rating.
Table 3.3 Current Draw Worksheet for SD SLC Devices
Current per Device
Standby:
Alarm:
Standby:
Alarm @ 25V:
Alarm @ 70V:
Standby:
Alarm:
Standby:
Alarm:
Standby:
Alarm:
Standby/Alarm:
Standby/Alarm:
Standby/Alarm:
Standby/Alarm:
Standby/Alarm:
Standby:
Alarm:
Standby:
Alarm:
Standby:
Alarm:
Alarm/Standby:
Alarm/Standby:
Alarm/Standby:
Alarm/Standby:
24 VDC
One input circuit:
Both input circuits: 30 mA
Alarm:
Alarm:
Alarm:
Alarm:
Total standby AH
Total alarm AH
Total ampere hours
required
6820 / 6820EVS Manual P/N LS10144-001SK-E:C 09/28/2017
Standby
Current
10 mA
mA
10 mA
52 mA
mA
275 mA
310 mA
70 mA
mA
100 mA
10 mA
mA
25 mA
100 mA
mA
150 mA
10 mA
mA
10 mA
mA
21 mA
mA
53 mA
mA
79 mA
mA
93 mA
mA
136 mA
98 mA
mA
155 mA
55 mA
mA
100 mA
mA
mA
mA
mA
mA
mA
mA
mA
15 mA
mA
mA
mA
mA
mA
A
H
AH
AH
x 1.25
Alarm
Current
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
A
H
AH

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Silent knight 6820Silent knight 6820evs

Table of Contents