The control panel recognizes when an SK detector or SK module is installed. For this reason, SK detectors can be assigned any unique
address from 1 to 159, and SK modules can be assigned any unique address from 1 to 159. There can be an SK detector using address 1
and an SK module using address 1.
0 is an invalid address. In order to set the sensor above address 99, carefully remove the stop on the upper rotary switch with thumb as
shown in Example 2.
Example 1: To select device address 35, turn the ONES rotary dial to 5 and the TENS rotary dial to 3 as shown in Figure 7.5.
Example 2: To select device address 105, turn the ONES rotary dial to 5 and the TENS rotary dial to 10 as show in Figure 7.5.
7.8 Wiring SD SLC Detectors
The information in this section applies to the following SD models, see Table 7.2 for list of devices.
To Wire SD Detectors:
1.
Wire device bases as shown in Figure 7.6.
2.
Set the address for each device as described in Section Figure 7.9.
7.9 Addressing SD SLC Devices
This section tells how to address detectors and modules. See Table 7.2 for a list of detectors that are easily addressed at the FACP. The
Installer Code is required to perform this task.
6820 / 6820EVS Manual P/N LS10144-001SK-E:C 09/28/2017
All dials labeled for ONES
or TENS position.
Figure 7.5 SK SLC Device Addressing Using Rotary Dials
Figure 7.6 Heat or Smoke Detector Connection to the FACP
Example 2: Device Set to 105.
93