4: Priority Rules; 5: Other Priority Considerations; Operation Mode Behavior - Honeywell Silent Knight SK318PT Installation And Operation Manual

Addressable fire system, emergency voice system
Table of Contents

Advertisement

NOTE: Status Points, Status Voice Aux 1, Status Voice Aux 2, and Background Music are contained within the System Status event priority.
NOTE: All fire, emergency and system troubles are prioritized into the Trouble event priority
10.5.4 Priority Rules
1.
Event priorities can be changed only within, not between, priority levels (defined by bold lines in Table 10.1).
2.
Emergency LOC Alarm must always higher than Emergency 1-8 Point Alarm and Emergency Voice Aux 1-4 Alarm.
3.
EVS events do not need to be in order by EVS number.
10.5.5 Other Priority Considerations
There are other considerations to take into account when the same event is acting on the same output group (an event being mapped to an
output group.) These are prioritized in order of appearance:
Event priority is considered here based on the Event Priority Table.
If an output group is mapped both directly and through an output group template to an event, the direct map gets priority. Example:
Template 1 Contains Group 1. Zone 1 Manual Pull is mapped to Template 1 and Group 1 using constant and ANSI patterns
respectively. If Zone 1 Manual Pull is active, Group 1 will output ANSI.
When an event is mapped to an output group from multiple zones, the lower numbered zone gets priority. Example: Zone 1 Manual
Pull and Zone 2 Manual Pull are mapped to Group 1 using constant and ANSI patterns respectively. If Zone 1 and Zone 2 Manual
Pull events are active, Group 1 will output constant.

10.6 Operation Mode Behavior

The control panel can be in one or more of seven conditions at any given moment: Normal, Alarm, Prealarm, Supervisory, Trouble,
Silenced, and Reset. Table 10.2 describes the behavior of the panel in each of these modes.
When looking at the LCD, the screen will display FIRE for the "Fire System", CO for the "CO System" and EMGY for "Emergency
Communication System". The highest priority event will display first and include the event count.
142
CO Alarm
Fire Pre-Alarm
Fire Interlock Alert
Fire Supervisory
CO Supervisory
Trouble
Site F Key Status
System Status
Table 10.1 : Event Priority Table
Emergency Voice Aux 4 Alarm
Emergency Supervisory
6820 / 6820EVS Manual P/N LS10144-001SK-E:C 09/28/2017

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Silent knight 6820Silent knight 6820evs

Table of Contents