List Of Sd Slc Devices; Swift® Wireless Slc Devices; Maximum Number Of Devices - Honeywell Silent Knight SK318PT Installation And Operation Manual

Addressable fire system, emergency voice system
Table of Contents

Advertisement

SK
Part Number
SK-HEAT-W
SK-HEAT-ROR-W
SK-HEAT-HT-W
Color Guide: -IV = Ivory color, -BL = Black, -WH = White, -WHITE-White

7.2 List of SD SLC Devices

The following SD SLC devices can be used with the control panel. SD detector bases are sold separately. See the appropriate section
number in this manual or the device installation instructions (packaged with the device) for more information.
NOTE: The control panel supports the use of either SD SLC devices or SK SLC devices. You cannot install both SLC device types on this
control panel.
SD
Model Number
SD505-PHOTO
SD505-HEAT
SD505-6AB
SD505-6IB
SD505-6RB
SD505-6SB
SD505-DUCT
SD505-DUCTR
SD500-PS/-PSDA
SD500-AIM
SD500-MIM
SD500-ANM
SD500-ARM
SD500-SDM
SD500-LIM
SD505-DTS-K
7.3 SWIFT
Wireless SLC Devices
®
The WSK-WGI Wireless Gateway acts as a bridge between a group of wireless fire devices and a SLC loop on
6820EVS. It is powered by the SLC loop or by a regulated, external 24VDC UL-listed power supply. For updated information about
wireless devices, system setup and operation see the SWIFT Smart Wireless Integrated Fire Technology Manual # LS10036-001SK-E
for more information.

7.4 Maximum Number of Devices

The 6820/6820EVS supports SK, SD or SWIFT SLC devices. The maximum number of SLC devices per system varies depending on
device protocol. The number of SLC expanders is limited only by the SBUS bandwidth, point count, and 1A SBUS current limit. Device
support is as follows:
SK Devices–The 6820/EVS supports a total of 1,110 SK points. The SLC points can be all sensors or all modules or any
combination of modules and sensors. SK devices are supported on the 6815 or the internal SLC.
OR
SD Devices–The 6820/6820EVS system can support a total of 635 SD devices, in any combination. SD devices are supported on
the 5815XL or the internal SLC.
OR
6820 / 6820EVS Manual P/N LS10144-001SK-E:C 09/28/2017
Fixed temperature thermal detector (135°F). White
Rate-of-rise thermal detector with 135° fixed temperature. White
Fixed high temperature thermal detector (190°F). White
Table 7.1 SK SLC Devices
Photoelectric smoke detector.
Absolute temperature heat detector. Trip point range from 135°F–150°F (0°C–37°C).
6" base
6" short circuit isolator base
6" relay base
6" sounder base
Duct Smoke Detector. Duct Housing including the SD505- Analog Photoelectric Smoke
Sensor. Intake tubing for duct available in three lengths: SD505-T2 (2.5 foot); SD505-T5
(5 foot); SD505-T10 (10 foot)
Duct Detector housing with relay base. Duct housing with relay base including SD505-
Analog Photoelectric Smoke detector pre-installed
Single or dual action addressable pull station
Addressable input module (switch input), standard size, DIP switch configurable
Mini input monitor module (switch input), small size, DIP switch configurable.
Addressable notification module
Addressable relay module DIP switch configurable.
Addressable smoke detector module.
Line isolator module. Fits in a double gang box.
Remote test switch & LED indicator for the SD505-DUCTR
Table 7.2 : SD SLC Devices
Model Name/Description
Model Name/Description
Installation
Instruction PN
I56-6529-00
I56-6529-00
I56-6529-00
Installation
Instruction PN
150955
I56-3541-00
I56-3542-00
I56-3540-00
1700-09882
1700-09882
I56-3632-00
I56-3547-00
I56-3544-00
I56-3545-00
I56-3546-00
I56-3543-00
1700-09882