Chapter 1
Install the Shelf and Backplane Cable
When installing the ONS 15454, the ground connection must always be made first and disconnected
Warning
last.
Figure 1-10 Cisco ONS 15454 Power Terminals
Return leads (black)
Remove or loosen the #8 power terminal screws on the ONS 15454. To avoid confusion, label the cables
Step 4
connected to the BAT1/RET1 (A) power terminals as 1, and the cables connected to the BAT2/RET2 (B)
power terminals as 2.
Note
Caution
Caution
Strip 1/2 inch (12.7 mm) of insulation from all power cables that you will use.
Step 5
Crimp the lugs onto the ends of all power leads.
Step 6
March 2003
RET 1
BAT 1
CAUTION: Remove power from both
the BAT1 and terminal blocks
prior to servicing
Use only pressure terminal connectors, such as ring and fork types, when terminating the battery,
battery return, and frame ground conductors.
Before you make any crimp connections, coat all bare conductors (battery, battery return, and
frame ground) with an appropriate antioxidant compound. Bring all unplated connectors,
braided strap, and bus bars to a bright finish, then coat with an antioxidant before you connect
them. You do not need to prepare tinned, solder-plated, or silver-plated connectors and other
plated connection surfaces, but always keep them clean and free of contaminants.
When terminating power, return, and frame ground, do not use soldering lug, screwless
(push-in) connectors, quick-connect, or other friction-fit connectors.
Battery leads (red)
RET 2
BAT 2
-42 V
24 A
SUITABLE FOR MOUNTING ON
A NON-COMBUSTIBLE SURFACE.
PLEASE REFER TO INSTALLATION
INSTRUCTIONS.
Cisco ONS 15454 Procedure Guide, R4.0
NTP-A6 Install the Power and Ground
1-27