When using T-taps, the total length of all taps and the main bus must be met in addition to the maximum distance requirements for the
various wire gauges.
7.7.1 Wiring 5815XL or 6815 in Style 6 & 7 (Class A) Configuration
Figure 7.3 illustrates how to wire the SLC loop for Class A installations.
NOTE: Style 6 does not use short circuit isolator devices
NOTE: Style 7 requires an isolator module as the first device on the in and the out loop
NOTE: No t-taps allowed on class A SLC loops
.
81
Figure 7.2 Calculating Wire Run Length for a T-tap
Figure 7.3 Class A SLC Configuration
IFP-300 / IFP-300ECS Manual P/N LS10145-001SK-E:B 12/18/2017