4.
Press the arrows to select the desired module. Refer to Section 8.5 for available choices. Then press ENTER.
Select an Output group
for this Zone/Group
Select a name for
the Point
5.
Enter the point number, then press ENTER.
6.
Press the up or down arrow key to select the type (notification or unused)., then press ENTER.
7.
Press the up or down arrow key to select the desired group., then press ENTER.
8.
Press ENTER to edit point name. See "Editing Text Using the Built-In Programmer" on page 195. Or, Press right arrow key to skip
point name edit.
9.
Repeat Steps 1 through 8 for all output points.
10. To use 5880 as Input point, Enter point number 41 - 48. (See Figure 9.5). Then press ENTER.
11. Press the up or down arrow key to select type (switch or unused), then press ENTER.
12. Press the up or down arrow key to select the desired function. (See Figure 9.5), then press ENTER.
13. If the point supports latching press the up or down arrow key to select latching or non-latching, then press ENTER.
14. Press the up or down arrow key to select the desired group/zone, then press ENTER.
15. Edit point name Or Press right arrow key to skip module name edit.
16. Repeat steps 10 through 15 for all input points.
9.5.5 Point Programming for 5496
To program module points:
1.
Enter the installer code. The panel will automatically go to the main menu.
2.
Select 7 for Panel Programming.
3.
Press 4 to enter point menu.
4.
Press the up or down arrow key to select the desired module. Refer to Section 8.5 for available choices, then press ENTER.
Select a name
for the Point
5.
Enter the point number, then press ENTER.
6.
Press the up or down arrow key to select the type (See Figure 9.6 on page 122). Then press ENTER.
7.
Press ENTER to edit point name. See "Editing Text Using the Built-In Programmer" on page 195 or Press right arrow key to skip
point name edit.
8.
Repeat Steps 1 through 7 for all points.
IFP-300 / IFP-300ECS Manual P/N LS10145-001SK-E:B 12/18/2017
Enter Point
Figure 9.4 Programming Points as Outputs for the 5880 Module
Select Switch or Unused
Figure 9.5 Programming Points as inputs for the 5880 Modules
Enter Point
Figure 9.6 Programming Points Screen for the 5496 Module
Select NOTIF
or UNUSED
Select Function
Select AUX DOOR, CONSTANT, AUX POWER
SYNC or AUX RESET