This section of the manual describes how to manually program the control panel from the built-in annunciator. Each subsection discusses
these menu options in detail. All options described in this section can be performed using the HFSS Honeywell Fire Software Suite.
Before any customized programming is done, JumpStart should be run first. After JumpStart is run, thoroughly test the
system. The reason the system should be tested after JumpStart is because JumpStart automatically programs the system,
searching for and configuring all SLC and SBUS devices it finds. JumpStart allows you to confirm the integrity of the
installation prior to performing any custom programming. After determining that the hardware is properly installed, custom
programming can be performed.

9.1 UL 864 / UL 2572 Programming Requirements

NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION, AND OTHER INVOLVED PARTIES:
This product incorporates field programmable software. In order for the product to comply with the requirements in the
Standard for Control Units and Accessories for Fire Alarm Systems, UL 864 and UL 2572, certain programming features or
options must be limited to specific values or not used at all as indicated below.
Programming
Option
Time Options
Time Options
Display Oldest Event Y (Enabled)
Initial Delay
Inter Message Delay 4-32
Alarm Verification
Auto Reset
ECS MIC Triggered
Event
ECS Input
Event Priority

9.2 Modules

This section lists the options available under the module option in the program menu. The following modules are available for the con-
trol panel: RA-100, RA-1000, & RA-2000 LCD annunciators, 5815XL SLC loop expander for SD devices, 6815 SLC Loop Expander
for IDP or SK devices, 5824 serial/parallel printer interface module, 5496 NAC Expander, RPS-1000 intelligent power module, 5880
LED I/O module, 5865 LED annunciator, ECS-50W, ECS-125W, ECS-INT50W or ECS-DUAL50W watt audio amplifier, ECS-VCM
voice control module, ECS-NVCM network voice control module, ECS-RVM remote voice module, and SK-NIC network interface
card.
9.2.1 Edit Modules
The features that can be edited when this option is selected are, module name, and class of wiring (Class A or Class B).
To edit an existing module, follow these steps:
1.
Enter the installer code.
2.
Select 7 for Program Menu.
NOTE: If you are working on a networked system you will need to select which panel you want to program
3.
Press 1 to enter module menu.
4.
Press 1 to edit a module.
5.
Use the up or down arrow to select the module you wish to edit. Then press ENTER.
109

Section 9: Programming

Permitted
in
Menu Item
UL 864
(Y/N)
Auto-resound
Yes
Low AC Report
Yes
Delay
Yes
N (Disabled)
No
0-28
Yes
No
Alarm
Yes
Verification
Auto Reset
Yes
ECS MIC
Triggered
Event
ECS Input
Yes
CO Alarm
No
IMPORTANT!
Permitted
in
Possible Settings
UL 2572
(Y/N)
Yes
4 hrs, 24hrs
Yes
0–30 hours
Yes
Yes & No
No
Yes & No
Yes
0-28
No
4-32
Yes
60-250
(Confirmation
period)
Yes
Never
Timer Event
Disabled
Yes
Latching
Non-Latching
No
Yes & No
IFP-300 / IFP-300ECS Manual P/N LS10145-001SK-E:B 12/18/2017
Settings
Settings
Permitted in
Permitted in
UL 864
UL 2572
4 hours if using
4 hours if using
SWIFT devices
SWIFT devices
1–3
1–3
Yes
Yes
No
No
3
3
4-32
4-28
60
60
Never
Never
Timer Event
Timer Event
Disabled
Disabled
Latching
Latching
No
No