2: Daytime/Nighttime Sensitivity; 3: Holiday Days - Honeywell Farenhyt Series Installation And Operation Manual

Addressable fire alarm control system emergency communication system
Hide thumbs Also See for Farenhyt Series:
Table of Contents

Advertisement

2.
Select 7 for Panel Programming.
3.
Select 5 for System Options.
4.
From the next menu, select 1 for Communication Options.
5.
Select 5 for phone line Gains
6.
The available options: *default
Dialing Gain:
Low = 9 DB Attenuation
Normal = 6 DB Attenuation
*High = 3 DB Attenuation
Reporting Gain:
*Low = 9 DB Attenuation
Normal = 6 DB Attenuation
High = 3 DB Attenuation
9.6.2 Daytime/Nighttime Sensitivity
If you need to change the time that sensitivity levels take effect (that is, the time that "Day" and "Night" begin, as well as the days of the
week), follow these steps.
1.
Enter the installer code.
2.
Select 7 for Program Menu.
3.
Select 5 for System Options.
4.
Select 2 for Day/Night Sense.
A screen similar to the one shown in "Changing Day/Night Sensitivity Time and Days" on page 128 will display.
9.6.3 Holiday Days
Up to 18 dates can be designated as holidays. When day/night sensitivity is enabled, all photoelectric smoke detectors in the system will
use night sensitivity for the entire day on days designated as holidays (see Section "Daytime/Nighttime Sensitivity" on page 128).
To add or change a holiday, follow these steps.
1.
Enter the installer code.
2.
Select 7 for Program Menu.
3.
Select 5 for System Options.
4.
Select 3 for Holiday Days.
A screen similar to that shown in "Select Holidays Screen" on page 128 will display.
Preprogrammed
holidays
Programmable
holiday locations
NOTE: For most installations, holiday programming will need to be performed each year to ensure correct dates.
IFP-300 / IFP-300ECS Manual P/N LS10145-001SK-E:B 12/18/2017
Figure 9.12 Changing Day/Night Sensitivity Time and Days
Figure 9.13 Select Holidays Screen