Select Key Leds; 2: Gaining Ecs Control; Loc Priority; Loc Lockout - Honeywell Farenhyt Series Installation And Operation Manual

Addressable fire alarm control system emergency communication system
Hide thumbs Also See for Farenhyt Series:
Table of Contents

Advertisement

Select Key LEDs

The Select Key LEDs are used to indicate which output areas are active for a microphone page or system events.
1.
Green LEDs: active areas for microphone paging.
NOTE: These are only active when the microphone PTT (Push To Talk) is engaged. Blinking indicates one or more associated network page
destination panels are unable to output the page
2.
Red LEDs: active areas for system events.
Select
LEDs
Select
Keys
11.2.2 Gaining ECS Control
When attempting to gain ECS Control, there are three things that govern whether or not ECS Control can be obtained:
1.

LOC Priority.

2.

LOC Lockout.

3.
User profile access control.
LOC Priority
LOCs are assigned (through panel or HFSS Honeywell Fire Software Suite programming of the ECS-VCM, ECS-NVCM or ECS-RVM)
an LOC priority of low, normal, or high. LOCs with a higher priority are always able to gain control from a lower priority LOC.
LOC Lockout
When LOCs are programmed to the same priority, the setting LOC lockout applies. LOC lockout will not allow an LOC to gain ECS
Control from the LOC with ECS Control until one of three things happen:
1.
The LOC lockout timer expires. Once the LOC lockout timer expires, an attempt to gain ECS Control can be made again.
NOTE: The lockout timer must be programmed to expire sometime other than Never.
2.
The user at the second LOC requests ECS Control from the LOC with ECS Control and that LOC grants the request. (See Section
11.2.7). If the ECS lockout timer expires while an ECS Control request is in progress, the system will automatically pass ECS
Control to the requesting LOC.
3.
The user at the second LOC enters an access code with the ECS Super User profile option.
The LOC lockout timer can be set between immediate and 12 hours in increments of 1 second or it can be set to never expire. The default
setting is 30 seconds. The LOC lockout timer is restarted upon any key press at the LOC with ECS control. The LOC lockout timer is
cleared when ECS Control is relinquished.
IFP-300 / IFP-300ECS Manual P/N LS10145-001SK-E:B 12/18/2017
NON-ACTIVE CALL
ALL CALL
Key
Key
READY
TO TALK
Figure 11.1 ECS-NVCM/ ECS-RVM Front View
ECS Control
ECS Control LED
Key
ECS CONTROL
Message
Keys
Message
LEDs
150