5880 Led I/O Module; 1: 5880 Board Layout - Honeywell Farenhyt Series Installation And Operation Manual

Addressable fire alarm control system emergency communication system
Hide thumbs Also See for Farenhyt Series:
Table of Contents

Advertisement

8.
If you are using a serial printer, use the next screen to select serial port options as required for your printer. Refer to your printer
manual if you need more information.

4.11 5880 LED I/O Module

The 5880 is an LED driver board that can be used in a wide variety of applications, including as an interface with most customized floor
plan annunciator boards. The 5880 can drive up to 40 LEDs and has one PZT controller. The 5880 also has eight inputs for dry contact
monitoring. The following sub-sections describe hardware installation. Refer to Section 9 for programming information.
4.11.1 5880 Board Layout
Figure 4.33 is a picture of the 5880 board showing locations of screw terminals for connection to the panel and contact monitor wiring;
pin connectors for connecting LEDs; and the DIP switch for selecting an SBUS ID number.
IFP-300 / IFP-300ECS Manual P/N LS10145-001SK-E:B 12/18/2017
Option
Baud Rate:
75 - 19200
Data Bits:
5 - 8
Stop Bits:
.5, 1, 2
Parity:
None, Even, Odd
Dry Contact Inputs - Supervised/Power Limited
SBUS Connection
Figure 4.33 5880 Board Layout
Choices
SBUS Address
DIPs
44