Add the 5815XL module to the system through programming. JumpStart
can also add it manually (see Section 9.2.2). Select a name, if desired (See "Naming Modules" on page 110.).
You are now ready to connect SLC devices to the 5815XL (see Section 7.6).
Figure 4.27 is a drawing of the 5815XL board, showing the location of terminals and DIP switches.
4.8.1 5815XL Connection to the Panel
Connect the 5815XL to the control panel as shown in Figure 4.28. After the 5815XL is connected to the panel, it
must be added to the system. This programming steps are described in Section 9.2.2.

4.9 6815 Installation

The 6815 SLC expander lets you add additional addressable devices. The maximum number of SLC devices per panel is 300. The num-
ber of 6815's is limited by the maximum number of SBUS devices.
NOTE: 6815 will support IDP, SK or SWIFT SLC devices.
41
DIP switches for
setting IDs
To panel via SBUS
Figure 4.27 5815XL Board
Figure 4.28 5815XL Connection to Main Panel Assembly
IFP-300 / IFP-300ECS Manual P/N LS10145-001SK-E:B 12/18/2017
®
will add the module automatically (see Section 8.1). You
To SLC loop
Supervised
Power Limited