Using The Addressable Relay Module For City Box Connection - Honeywell Farenhyt Series Installation And Operation Manual

Addressable fire alarm control system emergency communication system
Hide thumbs Also See for Farenhyt Series:
Table of Contents

Advertisement

4.
Program the NAC circuit used as a continuous and non-silencing. Refer to Section 9.5 for point programming, Section 9.4 for group
settings, and Section 9.3 for zone settings and mapping. It is not possible to reset the remote indication until you clear the condition
and reset the control panel.

4.18 Using the Addressable Relay Module for City Box Connection

Wire the Relay module as shown in Figure 4.48.
UL listed
EOL must be
Installed in City
Box Enclosure
55
Intended for connection to a Polarity Reversal circuit of a Remote
Station receiving unit having compatible ratings.
Note:
NAC Circuit 2 Used
as an example.
Any NAC circuit
could be used.
Note: The shunt connection is recognized only as a supple-
mentary signaling unit as part of a local control unit and is
not recognized as an auxiliary control unit connection per
Figure 4.47 City Box Connection
Figure 4.48 Relay Module for City Box Connection
IFP-300 / IFP-300ECS Manual P/N LS10145-001SK-E:B 12/18/2017
Non-Power Limited
Non-Supervised