To install the 6815:
1.
Make sure power is off at the panel.
2.
Mount the 6815 in the IFP-300/ECS cabinet, the RPS-1000 cabinet, or the 5815RMK remote mounting kit. Use the standoffs
located under the control panel board assembly and secure with screws provided with the 6815. For additional information see
Model RPS-1000 Installation manual (P/N 151153) or 5815RMK Remote Mounting Kit Installation Instructions (P/N 151391).
3.
Connect the 6815 to the control panel. (See Section 4.9.1.)
4.
Use on-board DIP switches to select an SBUS ID#. (See Section 4.13.1.)
5.
Add the 6815 module to the system through programming. JumpStart will add the module automatically (see Section 8.1). You can
also add it manually (see Section 9.2.2). Select a name, if desired (See "Naming Modules" on page 110.).
You are now ready to connect SLC devices to the 6815. Figure 4.29 is a drawing of the 6815 board, showing the location of terminals
and DIP switches.
4.9.1 6815 Connection to the Panel
Connect the 6815 to the control panel as shown in Figure 4.30. After the 6815 is connected to the panel, it must be added to the system.
This programming steps are described in Section 9.2.2.
IFP-300 / IFP-300ECS Manual P/N LS10145-001SK-E:B 12/18/2017
To panel via SBUS
Figure 4.29 6815 Board
Figure 4.30 6815 Connection to Main Panel Assembly