10.3.2 Using the Menus
To move through the menus:
To select an option:
Exit menu

10.4 Basic Operation

10.4.1 Setting Time and Date
1.
Select 4 for Set Date & Time.
2.
Make changes in the fields on the screen. Use right arrow to move through the fields. Use the up or down arrow key to select
options in the fields.
3.
When the date and time are correct, press ENTER.
10.4.2 Disable / Enable a Point
1.
Select 2 for Point Functions.
2.
Select 1 for Disable/Enable Point.

Disable / Enable NACs by Template

1.
Press 1 for Disable NACs by Template, or press 2 to Enable NACs by Template.
2.
Use the up or down arrow key to move through the list of templates. Press ENTER to select the current template.

Disable / Enable NACs by Group

1.
Press 3 to Disable NACs by Group, or press 4 to Enable NACs by Group.
2.
Use the up or down arrow key to move through the list of groups. Press ENTER to select the group highlighted.

Disable / Enable Zone Points

1.
Press 5 to Disable Zone Points, or press 6 to Enable Zone Points.
2.
Use the up or down arrow key to move through the list of zones. Press ENTER to select the zone highlighted.

Disable / Enable Point

1.
Press 7 to Disable /Enable Point.
2.
Choose Module.
3.
Use the up or down arrow key to choose point and press ENTER.
4.
Press right arrow to disable or enable point.

Inhibit Output Group

Inhibiting an output group prevents the group from being utilized by system mapping. While inhibited no event in the system can acti-
vate the output group.
1.
Press 8 to inhibit output group.
2.
Use the up or down arrow key to select the group to be inhibited.
3.
Press right arrow to inhibit the group.
4.
Press right arrow again to enable the group.
10.4.3 View Event History
Use the View Event History feature to display events on LCD. From the Main Menu, press 3 to select Event History. Events will begin
displaying with most recent events first.
The panel can store up to 1000 events. When it reaches its 1000-event capacity, it will delete the oldest events to make room for the new
events as they occur. In networked setups, each panel stores up to 1000 of its own events. When viewing Event History in the panel, the
newest 500 events from every panel in the site will be displayed. When using HFSS Honeywell Fire Software Suite, all 1000 events from
every panel in the network will be uploaded.
On multi-site displays, pressing ENTER or right arrow brings you directly into View Event History and allows you to view the Event
History from every panel in each of the sites that the multi-site display is assigned to.

To clear the event history

From the Installer menu select 1 for System Tests. From the test menu select 6 Clear History Buffer. In network systems, this clears the
History Buffer of all panels in the site.
10.4.4 Conduct a Fire Drill
1.
From the Main Menu, press 1 for System Tests.
2.
Press 1 for Fire Drill. You will be prompted to press ENTER.
3.
The drill will begin immediately after you press ENTER.
135
Use up and down arrow to move through the options in a menu. Use
a previous menu.
Enter the number of the option, or press ENTER if the option has the = symbol next to it.
Left arrow
IFP-300 / IFP-300ECS Manual P/N LS10145-001SK-E:B 12/18/2017