CHAPTER 4 - INSTALLATION INSTRUCTIONS
12.
CONTROL CARD SENSOR DRIVE MODULE
CONFIGURATION

12.1 General

The sensor drive modules fitted to the Single Channel Control Cards
have configuration links that effect the operation of the sensor. The
following sections identify the links to allow the configuration to be
inspected.

12.2 Single Channel Control Card, Catalytic Input Link Settings

Incorrect setting of the Sensor Drive Module, Catalytic current
range links may cause permanent damage to the sensor.
The Sensor Drive Module, Catalytic has three solder link positions (LK1
to LK3) which allow setting of the bridge current range. The following
ranges are available:
Range
1
219mA to 283mA
2
66mA to 230mA
3
118mA to 182mA
4
70mA to 134mA
S/C - Short Circuit,
The above information is only provided to allow the configuration of the
Sensor Drive Module, Catalytic to be checked. The current range is
factory set and should not be altered without reference to the
SYSTEM 57 Technical Manual.

12.3 Single Channel Control Card, 4 - 20mA Input Link Settings

Incorrect setting of the Sensor Drive Module, 4 - 20mA
configuration links may cause permanent damage to the Control
Card, Sensor Drive Module or Sensor.
The Sensor Drive Module, 4 - 20mA is fitted with thirteen jumper links
(LK1 to LK13) which allow numerous different sensor configurations to
CAUTION
Current
CAUTION
4 - 23
5701 Control System
LK1
LK2
S/C
S/C
S/C
S/C
O/C
S/C
O/C
O/C
O/C - Open Circuit
LK3
S/C
O/C
O/C
O/C