Smoke Alarm Verification; Function Keys - Honeywell Farenhyt Series Installation And Operation Manual

Addressable fire alarm control system emergency communication system
Hide thumbs Also See for Farenhyt Series:
Table of Contents

Advertisement

Conditions Required for a Interlock Release Alarm Output Activation
Any release requires the activation of an interlock switch, and either a manual release switch or 2 activated addressable detectors. When
these conditions are met, the "Interlock Release Alarm" and "Detector Alarm" outputs will activate, and the "Interlock Release Alert"
outputs will deactivate.
Inputs
1st Addressable Detector
2nd Addressable Detector
Manual Release Station
Interlock/Pressure Switch

10.8 Smoke Alarm Verification

Figure 10.7 illustrates how the Smoke Alarm Verification cycle operates.
During the Confirmation Period if there is no alarm indication then the system will return to normal operation.

10.9 Function Keys

The function keys on the IFP-300/ECS have multiple features. Their macro key functionality can simplify the disabling, activating, or
inhibiting points or groups respectively. They can also be used as a status type activation event and for activating Map Inhibit. Each F-
Key macro can hold 50 events.
To access the F-Key Recording menu:
1.
From the idle screen, press and hold the F-Key for 5 seconds.
2.
Enter a PIN with F-Key macro recording privileges, if prompted.
IFP-300 / IFP-300ECS Manual P/N LS10145-001SK-E:B 12/18/2017
X
X
X
X
X
X
X
Table 10.5 Double Interlock Zone Operation
Figure 10.7 Smoke Verification Cycle
Output Results
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X