4.
Place the trim ring over the back box as shown in Figure 4.25.
5.
Attach the door assembly to the back box using screws provided.
6.
After the SBUS wiring to the annunciator is complete (described in Section 4.7.2), replace the electronic assembly in the back box.
Place the bezel over the back box and tighten the set screws on the bezel.
4.7.2 RA-2000 Connection to the Panel
Connect the RA-2000 to the panel as shown in Figure 4.26.

4.8 5815XL Installation

The 5815XL SLC expander lets you add additional addressable devices. The maximum number of SD SLC devices per panel is 254. The
number of 5815XL's is limited by the maximum number of SBUS devices.
NOTE: 5815XL will only support SD protocol devices on this panel.
To install the 5815XL:
1.
Make sure power is off at the panel.
2.
Mount the 5815XL in the IFP-300/ECS cabinet, or the 5815RMK remote mounting kit. Use the standoffs located under the control
panel board assembly and secure with screws provided with the 5815XL. For additional information see Model RPS-1000
Installation Instructions (P/N 151153) or 5815RMK Remote Mounting Kit Installation Instructions (P/N 151391).
3.
Connect the 5815XL to the control panel. (See Section 4.8.1.)
4.
Use on-board DIP switches to select an SBUS ID#. (See Section 4.13.1.)
IFP-300 / IFP-300ECS Manual P/N LS10145-001SK-E:B 12/18/2017
Figure 4.25 Installing Trim Ring
Figure 4.26 Model RA-2000 Connection to the Panel