4: Current Draw Worksheet Sd For Slc Devices - Honeywell Farenhyt Series Installation And Operation Manual

Addressable fire alarm control system emergency communication system
Hide thumbs Also See for Farenhyt Series:
Table of Contents

Advertisement

Multiply by the Derating Factor
1. The FACP can only support 5 devices w/LED's on. This current draw has been added to the panels alarm current.
2. The SK-DUCT housing contains a vacant mount for a SK-RELAY (sold separately). Current draw for the SK-RELAY is calculated
by increasing the SK-RELAY row of the calculation sheet by one for each SK-RELAY used with a SK-DUCT.
3. SK-BEAM-T draws a maximum of 500mA from Auxiliary power only when the test feature is used. this should be considered when
determining auxiliary power capacity but not calculated into current requirements for day to day operation.
4. If using door holders, you do not need to consider door holder current for alarm/battery standby, because power is removed during
that time. However, during normal operation, door holders draw current and must be included in the 6.0A total current that can be
drawn from the panel.
5. Use next size battery with capacity greater than required.
6. Total does not include isolator devices or accessory bases.
3.7.4 Current Draw Worksheet SD for SLC Devices
Use Table 3.4 to determine current requirements during alarm/battery standby operation when SD SLC devices are installed. The IFP-
300 FACP supports up to a total of 127 SD SLC devices per loop, consisting of any combination of devices.
For each device use this formula:
Fire Panel (Current draw from battery) 1
Addressable SLC Devices
SD500-AIM
SD500-MIM
SD500-ARM
SD500-PS
SD505-HEAT
SD505-PHOTO
SD500-ANM
SD500-SDM
SLC Accessory Bases
SD505-6RB
SD505-6SB
SD505-DUCTR
SD505-DTS-K
SD505-DUCT
SLC Isolator Devices
SD500-LIM
SD505-6IB
IFP-300 / IFP-300ECS Manual P/N LS10145-001SK-E:B 12/18/2017
Number of
Device
Devices
Table 3.3 Current Draw Worksheet for SK SLC Devices
Number of
Device
Devices
This column
(254 max.)
(127 max.)
Table 3.4 Current Draw worksheet for SD Devices
Current per Device
Total ampere hours required
Current per Device
X
This column
=
Standby:
Alarm:
Standby/Alarm:
Aux. Pwr Standby:
Alarm:
SLC
Standby/Alarm:
SLC
Standby/Alarm:
Aux. Pwr Standby:
Alarm:
Standby/Alarm:
Aux. Pwr Standby:
Alarm:
SLC
Standby/Alarm
Aux. Pwr Standby:
Alarm:
SLC
Standby/Alarm:
None, included with SD505-DUCTR worst case.
SLC
Standby/Alarm:
Standby/Alarm:
Standby
Current
x 1.25
1
.
Standby
Current
Current per number of devices.
190 mA
190 mA
250 mA
5
mA
.55 mA
mA
mA
mA
mA
mA
8 mA
60 mA
mA
.55 mA
mA
.55 mA
mA
20 mA
106 mA
mA
.082 mA
mA
1 mA
32 mA
mA
.082 mA
2
mA
20 mA
2
62 mA
mA
.5 mA
mA
.5 mA
mA
.092 mA
Alarm
Current
Alarm
Current
250 mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
20