2.
Select 6 for Network Programming.
3.
Press 6 to enter Communicator Options menu.
Communicator Assignments
Each panel on the IFP-300/ECS network specifies which network communicator is used for reporting. The network communicator capa-
bility of the IFP-300/ECS system allows all panels to use the same communicator providing an economical solution for reducing the
number of paths required for reporting purposes. A communicator is specified by panel number. The network communicators will be
used to report events according to the communicator report table.
Communicator Miscellaneous
When using the SIA reporting format, the communicator sends information according to the SIA Reporting Type. The selections for this
option are:
1.
pi modifier (default)
2.
Panel ID
Receiver Configuration
The IFP-300/ECS network can report events to as many as 68 receivers. See Appendix C for panel/receiver relationship numbers. Each
receiver can be assigned reporting credentials. When using a format that supports phone numbers, it can be up to forty digits long.
1.
From the main menu.
2.
Select 6 for Network Programming.
3.
Press 6 to enter Communicator Options menu.
4.
Select 3 for Receiver Configuration.
5.
Select Panel to Program and press ENTER.
6.
Enter the receiver number that you want to report to. The receiver numbers available will correspond with what panel number you
entered. Receiver numbers are populated based on panel number and audited to allow only the 4 appropriate receivers. See
Appendix C for receiver number.
Available Format choices are:
Communicator Reporting Table
The communicator Report Table specifies event reporting for each panel on the network. Each row in the table specifies a panel, event
types to report, primary and backup receiver numbers, and report by point or zone. Associated with the receivers are account number and
daily test option. The table can have up to 99 rows.
1.
From the main menu.
2.
Select 6 for Network Programming.
3.
Press 6 to enter Communicator Options menu.
4.
Select 4 for Communicator Reporting Table.
5.
Press * to add rows, Press ENTER to edit data
6.3 Voice Options
6.3.1 Edit Timers
1.
Enter the installer code. The panel will automatically go to the main menu.
IFP-300 / IFP-300ECS Manual P/N LS10145-001SK-E:B 12/18/2017
Reporting Format
Contact ID
SIA500
SIA8
SIA20
Ethernet
Cellular
eVance
UNUSED
Figure 6.1 Communicator Reporting
70