9.6 System Options

This section of the manual explains how to customize software options that affect general operation of the system. This includes such
items as: Communication Options, Daytime/Nighttime Sensitivity, Holiday Days, Time Options, Miscellaneous Options, Daylight Sav-
ing Options, Edit Banner, and SLC Family. Refer to each individual subsection for complete instructions.
9.6.1 Communication Options

Auto Test Time

To access the automatic communicator test time screen:
1.
Enter the installer code.
2.
Select 7 for Program Menu.
3.
From the Program Menu, select 5 for System Options.
4.
Press 1 for Communication Options.
5.
Select 1 for Auto Test Time.
6.
Enter the hour you desire the control panel to send an automatic test report (or press the up or down arrow), then press ENTER.
7.
Enter the minutes (or press the up or down arrow), then press ENTER.
8.
Select AM or PM by pressing the up or down arrow, then press ENTER.
9.
Select Report Time Interval by pressing the up or down arrow, then press ENER. Time Interval selections are 24hrs, 12hrs, 6hrs and
4 hrs.
NOTE: AM and PM are only available if the panel "Clock Options" are set for AMPM mode. Otherwise the clock is in military time and
AMPM is not selectable.

Phone Lines

To access the phone lines screen:
1.
Enter the installer code.
2.
Select 7 for Program Menu.
3.
From the Program Menu, select 5 for System Options.
4.
Select 1 for Communication Opts
125
Type Selections
UNUSED
SWITCH
Table 9.7 Point Programming Options for ECS-VCM, ECS-NVCM and ECS-RVM
Function Selections for
each Type
MANUAL PULL
WATERFLOW
FIRE SUPERVISORY
FIRE TAMPER
FIRE DRILL
SILENCE
RESET
P.A.S. ACK
ZONE AUX1
ZONE AUX2
SYSTEM AUX1
SYSTEM AUX2
MANUAL RELEASE
INTERLOCK
STATUS POINT
VOICE AUX STATUS 1-2
VOICE AUX ECS 1-4
Background Music
ECS INPUT
ECS TAMPER
ECS SUPERVISORY
IFP-300 / IFP-300ECS Manual P/N LS10145-001SK-E:B 12/18/2017
Comments
Refer to comments column of
"Programming Options for 6815
Modules" on page 118 for
description of these options.
Latch or Non-latching feature only
appears for WATERFLOW, FIRE
SUPERVISORY, FIRE TAMPER,
ZONE AUX1, ZONE AUX2,
SYSTEM AUX1, SYSTEM AUX2,
ECS INPUT, ECS TAMPER, and
ECS SUPERVISORY.
User also has ECS Event Number
1-8 option for ECS INPUT.
Only available when an ECS-
VCM or ECS-NVCM is installed in
the system to the ECS-VCM or
ECS-NVCM/ECS-RVM choice
part.