8: Slc Family; Jumpstart® Autoprogramming; Restore Defaults; Voice Options - Honeywell Farenhyt Series Installation And Operation Manual

Addressable fire alarm control system emergency communication system
Hide thumbs Also See for Farenhyt Series:
Table of Contents

Advertisement

NOTE: See "Editing Text Using the Built-In Programmer" on page 195 for instructions on how to edit banner.
5.
Select each character of a word by pressing the up or down arrow, then press the right arrow to move to the next character.
6.
When word or sentence is complete press ENTER to save the custom banner.
9.6.8 SLC Family
The IFP-300/ECS supports SD series, IDP series or SK series SLC devices. You must configure the IFP-300 to accept the protocol you
are installing.
NOTE: You cannot mix SD, SK and IDP Series SLC devices on the same system.
1.
Enter the installer code.
2.
Select 7 for Program Menu.
3.
Press 5 for System Options.
4.
Press 8 for SLC Family.
5.
Press the up arrow to select the desired SLC family type.
6.
Press ENTER to accept the displayed SLC family type.
NOTE: When changing SLC type the following message will appear:
NOTE: Message when changing SLC family from IDP or SK to SD: Changing to this SLC family will remove all external 6815's.
NOTE: Message when changing from SD to IDP or SK SLC family will remove all 5815XL's on the system.
9.7 JumpStart
AutoProgramming
®
JumpStart AutoProgramming is used to auto learn the system hardware after devices have been added or removed from
the system. Hardware devices which remain the same between repeat JumpStart will retain any customized text or options
associated with the device. It is best to carefully consider the network ID setting for each panel before the first JumpStart
AutoProgramming is performed. Once this is done the panel must be defaulted back to factory defaults if the network ID
settings need to change.
To run JumpStart AutoProgramming:
1.
Enter the installer code.
2.
Select 7 for Program Menu.
3.
Select 6 for JumpStart.
4.
Press ENTER to accept the warning screen.
5.
Follow the remaining on screen instructions
6.
Press ENTER to confirm. See Section 8.1.3

9.8 Restore Defaults

This option allows you to restore the panel back to factory defaults. All programming will be lost.
1.
Enter the installer code. The panel will automatically go to the main menu.
2.
Select 7 for Panel Programming.
3.
Select 7 for Restore Defaults.
4.
Press the up or down arrow key to select YES or NO from the warning screen. Then press ENTER.

9.9 Voice Options

Through this programming menu you can modify the messages programmed into an VCM. You can also modify other voice settings.
9.9.1 VCM Maintenance
The VCM Maintenance menu is used to program custom messages into the VCM. Messages can be recorded locally using the micro-
phone.
1.
Select 7 for Panel Programming.
2.
Select 8 for Voice Options.
131
Figure 9.15 SLC family change
IMPORTANT!
IFP-300 / IFP-300ECS Manual P/N LS10145-001SK-E:B 12/18/2017