* Automatic drift compensation is always in effect for all detectors. See Section
check if a detector is in compliance.
4.
Use the up or down arrow to scroll through the range or enter directly from the number keys on the annunciator, then press ENTER.
NOTE: If the SLC protocol is changed from IDP/SK to SD and a zone's sensitivity is higher than the SD limit, the zone sensitivity will be set to
the max value of 150 for the SD family.

Zone Accessory Options

1.
Do steps 1 through 5 of Section 9.3.1.
2.
Press 3 to edit the Zone's Accessory options.
Single or Multi-Station cadence pattern (choose from Patterns 00 to 02, 23 if using IDP or SK. Choose from 00-16, 23 if using SD
devices). See Appendix D.
CO Single and Multistation Cadence (choose from Cadence Patterns 00 to 02, 23 for IDP or SK devices).
NOTE: The B200S Sounder base provides the recommended CO cadence pattern
Local Zone (choose Y or N, for Yes or No).
NOTE: If the SLC protocol is changed from SD to IDP/SK series and the cadence is no longer valid for IDP/SK, the zone cadence will be set to
constant on.
9.3.2 View Zone Points
To view the points in a zone, follow these steps:
1.
Enter the installer code. The panel will automatically go to the main menu.
2.
Select 7 for Panel Programming.
3.
Press 2 to enter zone menu.
4.
Press 2 to view zone points.
5.
Enter the number of the zone you wish to view, then press ENTER

9.4 Group

An output group is made up of output points that have been programmed to respond in the same way. Output groups simplify program-
ming because you only have to program the output characteristics that are common to all of the group points once, instead of program-
ming each individual point. Once you have defined the characteristics of output groups, you can assign each point to the appropriate
group. All valid output points are assigned to only one output group. Unused points are not assigned to any output group. Up to 250 out-
put groups can be defined per panel.
9.4.1 Edit Group
In the edit group option you can program the name of an output group and change the properties of that group.
To edit a group, follow these steps:
1.
Enter the installer code. The panel will automatically go to the main menu.
2.
Select 7 for Panel Programming.
3.
Press 3 to enter group menu.
4.
Press 1 to edit group.
5.
Enter the number of the group you wish to edit, then press ENTER.

Edit Group Name

6.
To edit the group name, press 1.
You can use words to display a descriptive name for a group.
NOTE: See Appendix B for editing names.

Edit Group Properties

7.
To edit the group properties, Press 2 from the edit group menu.
NOTE: These settings only apply to non-voice groups
Select Y for voice group and N for non-voice group.
Select / Dynamic Activation switch number: used when the group is defined as a voice group; or as a non-voice group where
Dynamic Activation is used. This option links the output group with a voice select switch on a VCM, RVM, or switch expander for
dynamic activation/deactivation.
Template Override is shown when set to Yes.
Dynamic Activation -Is shown if a non-voice group is assigned to a Select/Dynamic Activation switch number
113
IFP-300 / IFP-300ECS Manual P/N LS10145-001SK-E:B 12/18/2017
for information about how to
10.4.11

Advertisement

Table of Contents
loading

This manual is also suitable for:

Farenhyt ifp-300Farenhyt ifp-300ecs

Table of Contents