To view event history:
1.
Press 3 to select Event History.
2.
Press the up or down arrow key to view events in the history buffer.

13.3 Built-in Troubleshooting and Testing Tools

The fire control panel has several built-in testing and troubleshooting tools that can be utilized to save time while testing and trouble-
shooting points and SLC devices.
13.3.1 SLC Device Locator
SLC device locator can be used to locate a device on a SLC loop.
Follow these steps to locate a particular SLC device:
1.
Select 2 for Point Functions from the Main Menu.
2.
Select 4 for SLC Single Device Locator.
A message similar to the one shown in Figure 13.1 will display.
3.
Press ENTER to accept, or left arrow to Exit.
If left arrow is chosen you will exit back to the Point Function menu.
If ENTER is chosen the system will cease normal operation leaving the premise unprotected.
4.
Select the SLC loop.
5.
Enter the SLC address of the device you wish to locate.
The LED on the selected device will start flashing.
6.
Press left arrow key to exit the SLC Device Locator.
NOTE: Once you exit, the system will resume normal operation.
13.3.2 SLC Multiple Device Locator
This feature is the same as SLC Single Device Locator, except you can locate up to 8 devices on a single search.
Follow these instructions to locate multiple SLC devices:
1.
Select 2 for Point Functions from the Main Menu.
2.
Select 5 for SLC Multiple Device Locator.
A message similar to the one shown in Figure 13.2 will display.
3.
Press ENTER to accept, or left arrow to Exit.
If left arrow is chosen you will exit back to the Point Function menu.
If ENTER is chosen the system will cease normal operation leaving the premise unprotected.
4.
Select the SLC loop.
5.
Enter up to 8 SLC addresses for the devices you wish to locate.
The LEDs on the selected devices will start flashing.
6.
Press the left arrow key to exit SLC Multiple Device Locator.
NOTE: Once you exit, the system will resume normal operation.
IFP-300 / IFP-300ECS Manual P/N LS10145-001SK-E:B 12/18/2017
Figure 13.1 Shut Down Warning
Figure 13.2 Shut Down Warning
176