Line Monitor
Enable the line monitor for each phone line that will be used. See "Phone Lines Editing Screen" on page 126 for location of this field on
the phone lines screen. When the phone line monitor has been enabled for a phone line, a trouble condition will occur if the line is not
connected. If a phone line will not be used, it must be disabled.
12. Select Y (monitor line) or N (don't monitor line) by pressing the up or down arrow, then press ENTER.
Answering Machine Bypass
This option is used in conjunction with the HFSS Honeywell Fire Software Suite. This feature ensures that an answering machine will
not interfere with communication between the panel and the computer. If an answering machine is used at the panel site, enable this fea-
ture; if an answering machine is not used, disable the feature.
This option is factory-programmed as Yes (enabled).
The selection made here must match the programming for this option in the Communication Configuration dialog box of the HFSS.
13. Select Y (answering machine bypass enabled) or N (answering machine bypass disabled) by pressing the up or down arrow, then
press ENTER.
Phone Line Unused
This option is used so that you can set unused phones lines to "Yes", so no auto-test will be sent through that line.
This option is factory programmed as No.
14. Select Y or N by pressing the up or down arrow key, then press ENTER.

Edit Ethernet

1.
Enter the installer code. The panel will automatically go to the main menu.
2.
Select 7 for Panel Programming.
3.
Select 5 for System Options.
4.
From the next menu, select 1 for Communication Opts.
5.
Select 3 for Edit Ethernet.

AlarmNet Timers

1.
Enter the installer code. The panel will automatically go to the main menu.
2.
Select 7 for Panel Programming.
3.
Select 5 for System Options.
4.
From the next menu, select 1 for Communication Opts.
5.
Select 4 for AlarmNet Timers.
6.
The available options for AlarmNet Timers are as follows: *default
• Ethernet: None, 75 seconds, 90 seconds, 3 minutes, *5 minutes, 1 hour, 24 hours,30 days.
• Cellular: None, *24 hours, 30 days.
• Old Alarm: None, 10 minutes, 15 Minutes,*30 Minutes, 1 Hour, 2 Hours, 4 Hours, 6 Hours, 12 Hours, 24 Hours. (Sets how long
an undeliverable alarm is retried for delivery to the central station. If the message is not validated, it is retried until the old alarm
time is reached or the message is validated).

Phone Line Gains

1.
Enter the installer code. The panel will automatically go to the main menu.
127
Figure 9.10 Edit Ethernet Message
Figure 9.11 AlarmNet Timers
IFP-300 / IFP-300ECS Manual P/N LS10145-001SK-E:B 12/18/2017