The AC terminals are rated at 120 VAC, 60 Hz, 3.6A.

4.3 Battery Power

The batteries must be sealed lead acid type. Before connecting the batteries to the FACP, make certain that the interconnect
cable between the batteries is not connected. Do not connect the battery jumper cable until the system is completely
installed. Observe polarity when connecting the batteries.
WARNING:
RISK OF PERSONAL INJURY
!
Battery contains sulfuric acid which can cause severe burns to the skin and eyes and can destroy fabrics. If contact is made with
sulfuric acid, immediately flush the skin or eyes with water for 15 minutes and seek immediate medical attention.
The control panel battery charge capacity is 7.0 to 35 AH. The main control cabinet can house batteries up to 18 AH, larger capacity bat-
teries can be housed in a RBB (see Section 4.3.1 for details). Use 12V batteries of the same AH rating. Determine the correct AH rating
as per your current load calculation (see Section 3.7).
Wire batteries in series to produce a 24-volt equivalent. Do not parallel batteries to increase the AH rating. It is recommended that you
replace batteries every five years.
IFP-300 / IFP-300ECS Manual P/N LS10145-001SK-E:B 12/18/2017
Figure 4.2 120VAC Power Connection
Battery Jumper
(P/N 140694)
Shipped With Panel
Figure 4.3 Battery Connection