LS10144-001SK-E
3.4
Electrical Specifications
Table 3-1: Terminal Descriptions and Electrical Specification
Terminal Label
L
AC input (hot)
Earth ground
N
AC input (neutral)
–
NAC 6
Flexput™ Circuits
+
–
NAC 5
Flexput™ Circuits
+
–
NAC 4
NAC Circuits
+
–
NAC 3
NAC Circuits
+
–
NAC 2
NAC Circuits
+
–
NAC 1
NAC Circuits
+
B
SBUS communication
A
SBUS OUT
+
SBUS power
-
B
A
SBUS IN
Used for Class A installations
+
-
B
A
EXT. Comm Cellular Connection
+
-
N.C.
C
RELAY 1
General Purpose Relay 1
N.O.
N.C.
C
RELAY 2
General Purpose Relay 2
N.O.
N.C.
C
TROUBLE
Trouble Relay
N.O.
Description
Voltage
120 VAC, 60 Hz
N/A
120 VAC, 60 Hz
24 VDC
24 VDC
24 VDC
24 VDC
24 VDC
24 VDC
5 VDC
24 VDC
input
24 VDC
24 VDC
24 VDC
3-2
Before You Begin Installation
Rating
Current
3.3 A
N/A
3.3 A
3.0A notification and auxiliary
power circuits
100 mA for initiation circuits
3.0A notification and auxiliary
power circuits
100 mA for initiation circuits
3.0A notification and auxiliary
power circuits
3.0A notification and auxiliary
power circuits
3.0A notification and auxiliary
power circuits
3.0A notification and auxiliary
power circuits
100 mA
1.0 A
55 mA, 100 mA
2.5 A, resistive
2.5 A, resistive
2.5 A, resistive
Earth
Ground
Faults
N/A
N/A
N/A
0
0
0
0
0
0
0
0
0
N/A
N/A
N/A