Model 6820 / 6820-EVS Installation Manual
7.7
Addressing SK SLC Devices
All SK devices are addressed using the two rotary dials that appear on the device board. Use the ONES rotary
dial to set the ones place in a one or two digit number, and use the TENS rotary dial to set the tens place in a two
or three digit number.
The control panel recognizes when an SK detector or SK module is installed. For this reason, SK detectors can
be assigned any unique address from 1 to 159, and SK modules can be assigned any unique address from 1 to
159. There can be an SK detector using address 1 and an SK module using address 1.
0 is an invalid address. In order to set the sensor above address 99, carefully remove the stop on the upper rotary
switch with thumb as shown in Example 2.
Example 1: To select device address 35, turn the ONES rotary dial to 5 and the TENS rotary dial to 3 as shown in
Figure 7-5.
Example 2: To select device address 105, turn the ONES rotary dial to 5 and the TENS rotary dial to 10 as show
in Figure 7-5.
All dials labeled for ONES
or TENS position.
Figure 7-5 SK SLC Device Addressing Using Rotary Dials
7.8
Wiring SD SLC Detectors
The information in this section applies to the following SD models, see Table 7-2 for list of devices.
To Wire SD Detectors:
1.
Wire device bases as shown in Figure 7-6.
Example 2: Device Set to 105.
7-7
LS10144-001SK-E