Single Interlock Zone Releasing - Honeywell 6820EVS Installation And Optimization Manual

Addressable fire system emergency voice system
Hide thumbs Also See for 6820EVS:
Table of Contents

Advertisement

Model 6820 / 6820-EVS Installation Manual
Manufacturer
Viking
* When ordering, order as P/N 7641-L8
10.7.1

Single Interlock Zone Releasing

A single interlock zone utilizes a minimum of two addressable detectors and a designated manual release switch.
Only addressable detectors can be used. No conventional detectors can be used.
Each Single Interlock Zone input requires at least one manual release switch.
Conditions Required for an Pre-Alarm Output Activation
If any single addressable detector is activated, the "Pre-Alarm" output will activate. This alerts the user that the
initial stages required for a release condition are present. (Also refer to Table 10-4.)
Conditions required for an General Alarm and Release Output Activation
If two or more addressable detectors, or a manual release switch activate, the "Alarm" and the "Release" outputs
Table 10-3: Approved Releasing Solenoids
Part Number
11591
11595
11592NC
16360
Figure 10-9 Wiring Configuration for Solenoid
Important!
10-17
Rated Voltage,
Rated Current,
DC
Milliamp
24 VDC
417
24 VDC
417
24 VDC
416
24 VDC
500
Model 7641-L8
Must Mounted
at the Solenoid
LS10144-001SK-E