LS10144-001SK-E

10.7 Releasing Operations

The control panel supports two types of releasing: Double Interlock Zone, and Single Interlock Zone. The
Double Interlock Zone operation requires an interlock switch input in the system, and the Single Interlock Zone
does not. An interlock switch is typically a dry-contact pressure switch.
When Single or Double Interlock Zone releasing is selected using HFSS Honeywell Fire Software Suite
software, the software suite will automatically default the following system parameters:
Note: The defaults created can be modified through programming if desired.
Output Group 2 is created. Output Group 2 will be defaulted as a "Detector Alarm" output group for all
releasing zones. NAC [98:001] is assigned to Output Group 2.
Output Group 3 is created. Output Group 3 will be defaulted as a "Interlock Release Alert" output group for
all releasing zones. NAC [98:002] is assigned to Output Group 3.
Output Group 4 is created. Output Group 4 will be defaulted as "Interlock Release Alarm" output group for
all releasing zones. NAC circuit [98:003] is assigned to Output Group 4.
Note: The installer must define which input points will be used for detectors, manual release switches, or inter-
lock/pressure switches.
Note: For manual release operation, Installer must use an FM approved/ UL listed releasing manual station.
Manufacturer
Asco
Honeywell/Skinner
Barnbrook System
Kidde Fenwal
Minimax
Nohmi Bosai
Parker Hannifin
Snap-tite
TLX
Versa Valves
Victaulic
Table 10-3: Approved Releasing Solenoids
Part Number
T8210A107
8210G207
HV2740607
HV2838521
HV2740608
701X7028
EA45
890181
486500
895630
897494
88 7363
88 5738
88 9323
R85M10
70610006
10610707
2823A-2NB-A4F6
2823A-2NB-A4F5
PA0036-A
CGS-4232-NB3-S2
753E
767
10-16
Rated Voltage,
Rated Current,
DC
Milliamp
24 VDC
700
24 VDC
442
24 VDC
375
24 VDC
375
24 VDC
375
24 VDC
917
24 VDC
200
24 VDC
2000
24 VDC
290
24 VDC
2000
24 VDC
1500
24 VDC
1040
24 VDC
1040
24 VDC
500
24 VDC
1200
24 VDC
417
24 VDC
417
24 VDC
458
12 VDC
917
24 VDC
600
24 VDC
438
24 VDC
364
24 VDC
364