Model 6820 / 6820-EVS Installation Manual
6.
When the wait message clears, the following options display:
1- for Read Address. Use to read (or check) a single detector's address.
2- for Write Address. Use to program a single detector's address.
3- for Seq. Programming. Use to program more than one detector in sequential order.
7.
If you are changing addresses, write the programmed address on the back of the device.
8.
To exit press left arrow until fully exited.
7.9.1

SLC Devices with DIP Switches

Input and relay module addresses are set using the DIP switches on the module board. The chart below shows the
available addresses. For example, to select address 3, place DIP switches 1 and 2 in the up position. The range of
valid addresses is 1-127. 0 is an invalid address.
Figure 7-8 SD SLC Device Addressing Using DIP Switches
7-9
LS10144-001SK-E