Wiring 5815XL or 6815 in Class A Configuration

Figure 7-3 illustrates how to wire the SLC loop for Class A installations.
Note: Class A wiring also requires an isolator module as the first device on the in and the out loops.
Note: No t-taps allowed on class A SLC loops.
7.6

Wiring SK SLC Detectors

This section describes how to install SK heat and smoke detectors. See Table 7-1 for a list of detectors. Refer to
the detectors' installation instructions for more detailed information.
To wire SK detectors:
1.
Wire device bases as shown in Figure 7-4.
2.
Set the address for each device as described in Section 7.7
Figure 7-4 Heat and Smoke Detector Connection to the Panel.
SK, SD and SWIFT™ Wireless SLC Device Installation
Figure 7-3 Class A SLC Configuration