Model 6820 / 6820-EVS Installation Manual
Term
Output Point
(or "Output Circuit")
Output Group (OPG)
Output (or "Cadence") Pattern
Mapping
EVS
Common Communication Link
SWIFT
1.3

Compatible Products

Table 1-1 lists the products available from Honeywell Silent Knight for use with the 6820 and 6820EVS.
Type of Device
SK Addressable
See Section 7.1 for a list of compatible devices.
SLC Devices
SD Addressable
See Section 7.2 for a list of compatible devices.
SLC Devices
SWIFT Wireless
See Section 7.3 for a list of compatible devices
SLC Devices
5815XL (Rev H or higher)
SLC Expander
6815 SLC Expander
5824 Serial/Parallel Printer
Interface Module
5895XL (Rev F or higher)
Intelligent Power Module
5496 (Rev F or higher)
Intelligent Power Module
6860 LCD Annunciator
Other Modules
5860 LCD Annunciator
6855 LCD Annunciator
5860TG and 5860TR Trim
Ring Kit
5865-3 and 5865-4 LED
Annunciator
5880 (Rev C or higher)
LED I/O Module
A notification point or circuit for notification appliances. Relay circuits and auxiliary power
circuits are also considered output points.
A group of output points. Operating characteristics are common to all output points in the
group.
The pattern that the output will use, for example, Constant, March Code, ANSI 3.41. Applies to
zones and special system events. See Appendix D for additional information.
Mapping is the process of specifying which outputs are activated when certain events occur in
the system. Section 8.2 explains mapping in detail.
Emergency Voice System.
Up to 17 panels can be linked. Consist of any combination of 17 panels of these model
numbers:6700, 6808, 6820, or 6820EVS. For reporting purposes only. Not a peer-to-peer
networked system.
Smart Wireless Integrated Fire Technology
Table 1-1: 6820 or 6820EVS Compatible Products
Model
Allows an additional 127 SD devices to be added to the system for a maximum
of 635 points. Supports SD devices only.
Allows an additional 159 SK modules and 159 SK sensors to be added to the
system for a maximum of 1110 points. Supports System Sensor SK devices only.
Allows a printer to be attached for the on-site event logging. Maximum of four
5824s per control panel.
Provides additional power, six Flexput™ circuits, and
two Form C relays. Max. 16 per system see Model
5895XL Installation Instructions P/N 151142.
Provides 4 additional Notification Appliance Circuits/
Auxiliary power. (Up to 16 per system).
4x40 backlit LCD remote fire annunciator Up to 16
any combination of annunciators per system
4x20 LCD remote fire annunciator. 5860 is gray;
5860R is red.
4x20 LCD remote fire annunciator
Trim ring kits for surface mounting the 5860 annunciator. 5860TG is gray;
5860TR is red.
LED annunciator can display up to 30 LEDs (15 red
and 15 yellow). 5865-4 has key switches for silence
and reset, and a system trouble LED.
Driver for up to 40 LEDs. Interfaces with customized
annunciator boards. In addition, the 5880 has eight
generic switch input points.
Description
Description
1-3
LS10144-001SK-E
5895XLs and 5496s can
be used in any
combination, up to a
total of 16 devices on
one system.
up to a total of 16 in any
combination on one
system.
5865-3, 5865-4, and
5880 can be used in any
combination, up to a
total of eight devices on
one panel.