5824 Serial/Parallel Interface Module Installation; Selecting 5824 Options - Honeywell 6820EVS Installation And Optimization Manual

Addressable fire system emergency voice system
Hide thumbs Also See for 6820EVS:
Table of Contents

Advertisement

Model 6820 / 6820-EVS Installation Manual

4.10 5824 Serial/Parallel Interface Module Installation

The 5824 serial/parallel interface module allows you to connect a printer to the panel, so you can print a real-time
log of system events, detector status and event history. Instructions for installing the 5824 appear below.
The 5824 and the printer connected to the 5824 Parallel port is ancillary, the serial port can be used for primary
fire signaling. The printer must be a UL 864 listed printer.
5824 installation involves the following steps:
1.
Make sure power is off at the panel.
2.
Connect the 5824 to the panel as shown in Figure 4-33.
Note: Four 5824s per panel maximum.
3.
Use the DIP switches on the back of the 5824 board to assign an ID# to the 5824 (see Section 4.13.1).
4.
Configure the 5824 device through programming. See Section 4.10.1.
5.
Connect a printer to the 5824 as shown in Figure 4-33.
Supervised
Power Limited
4.10.1

Selecting 5824 Options

Configuring the 5824 includes the following steps:
Add the module to the system. JumpStart® will add the module automatically (see Section 8.1). You can
also add it manually (see Section 9.2.2).
Select a name, if desired (see Section 9.2.1.2).
Select options for the printer and the output port. See below.
Printer and Output Port Options
1.
From the Installer Main Menu, select 7 for Program Menu.
2.
Select 1 for Module.
3.
Select 1 for Edit Module.
4.
From the list that displays, select the 5824 module you want to configure.
Figure 4-33 5824 Connection to the Panel