Model 6820 / 6820-EVS Installation Manual
4.9

6815 Installation

The 6815 SLC expander lets you add 159 SK detectors and 159 SK modules. The maximum number of SLC
devices per panel is 1110. The number of 6815's is limited by the maximum number of SBUS devices.
Note: 6815 will only support SK or SWIFT™ SLC devices.
To install the 6815:
1.
Make sure power is off at the panel.
2.
Mount the 6815 in the 6820 cabinet, the 5895XL cabinet, or the 5815RMK remote mounting kit. Use the
standoffs located under the control panel board assembly and secure with screws provided with the 6815.
For additional information, also see Model 5895XL Installation Instructions (P/N 151142) or 5815RMK
Remote Mounting Kit Installation Instructions (P/N 151391).
3.
Connect the 6815 to the control panel. (See Section 4.8.1.)
4.
Use on-board DIP switches to select an SBUS ID#. (See Section 4.13.1).
5.
The new 6815 module must be added to the system through programming. JumpStart will add the module
automatically (see Section 8.1). You can also add it manually (see Section 9.2.2). Select a name, if desired
(see Section 9.3.1.1).
6.
You are now ready to connect SLC devices to the 6815 (see Section 9.5.1).
Figure 4-31 is a drawing of the 6815 board, showing the location of terminals and DIP switches
4.9.1

6815 Connection to the Panel

Connect the 6815 to the control panel as shown in Figure 4-32. After the 6815 is connected to the panel, it must
Figure 4-31 6815 Board
4-23
LS10144-001SK-E