LS10144-001SK-E
If using the battery cable extenders provided (P/N 140643), mount the RBB cabinet no
more than 18" away from the main control panel cabinet. This will ensure that the bat-
tery cables reach the battery terminals.
2.
Connect the main control panel battery cables to the battery cable extenders as shown in Figure 4-5.
Figure 4-5 Splicing Control panel Battery Cable to RBB Battery Cable Extenders
3.
Run extended battery cable from control panel cabinet through conduit to RBB cabinet. See Figure 4-6.
Conduit
Coupler
Conduit
Note: Figure 4-6 is an example of how the wire connections can be routed. However, any other cabinet knock-
Mounting Holes
Figure 4-4 RBB Cabinet Mounting Holes
+
Figure 4-6 Battery Connections in the RBB Cabinet
Cabinet
RBB Cabinet
Cover Screws
-
+
RBB Cabinet
Cover Screws
4-4