Point; Point Programming For 5815Xl Module - Honeywell 6820EVS Installation And Optimization Manual

Addressable fire system emergency voice system
Hide thumbs Also See for 6820EVS:
Table of Contents

Advertisement

LS10144-001SK-E
9.5

Point

You may need to change characteristics of individual input points (detectors and switches) even after using
®
JumpStart
. This section explains how to change options for: type of point, latching/non-latching, silenceable/
non-silenceable, zone assignment (input points), detector accessory base options, group assignment (output
points), and point name.
9.5.1

Point Programming For 5815XL Module

To program points on 5815XL Module, follow these steps:
1.
Enter the installer code. The panel will automatically go to the main menu.
2.
Select 7 for Program Menu.
3.
Press 4 to enter point menu.
4.
Press the Up or Down arrows to select the desired module. Refer to Section 8.5 Quick Reference Table for
available choices. Press ENTER.
5.
Enter the number of the point you wish to edit, then press ENTER.
6.
Select the type of device by pressing the up or down arrow key. Refer to Table 9-3 under the column heading
"Type Selection" for a list of choices.
Type
Function
Selection
UNUSED
PHOTO
ION
HEAT
PHOTO DUCT
DETECTOR
2-WIRE SMOKE
PHOTO
SUP DET
ION
HEAT
PHOTO DUCT
Table 9-3: Programming Options for 5815XL Modules
Latching Option
Latching
Non Latching
Comments
Select for SLC points that are unused.
Spot photoelectric detectors.
Spot ionization detector.
Spot heat detector.
Duct photoelectric detector.
2-wire smoke detector.
Use this option when you want a detector to indicate a supervisory
alarm.
9-10
Programming