Troubleshooting; Specifications - Honeywell ADEMCO 6150RF ADEM Installation And Setup Manual

Keypad/transceiver
Hide thumbs Also See for ADEMCO 6150RF ADEM:
Table of Contents

Advertisement

Step
To change any of the programming for the wireless key, perform one
3.
of the following steps in the Programming for an Installation WITH
Local Wireless Keys section.
For the user code, perform step 5.
For the loop functions, perform steps 6 and 7.
For the on-board relay assignment, perform steps 8 to 10.
When you have completed editing the wireless keys, press the [✻] key
4.
twice to exit the Program mode.
* The keypad will display the last number that was enrolled (i.e., "d3")
Note: Upon exiting the Program mode, the 6150RF alternately flashes "Ad," the 2-digit keypad address, and the 2-digit receiver
address. If either of these is incorrect, repeat steps 1 through 3 in the Programming for an Installation Without Local Wireless
Keys section.

TROUBLESHOOTING

The following error messages cause the 6150RF to produce rapid beeps for 5 seconds. The table below describes the
error messages and the corrective actions.
Display
Probable Cause
Lb
Low battery in the wireless
key
OC
Open circuit
1C
Incompatible connection
Check 09 OR
1.
6150RF Receiver is not
communicating
Check 100 RF
Receiver OR
2.
Another device on the
keypad terminals is not
Check 10n RF
communicating to the
Receiver*
control panel
E8
Too many RF zones
programmed
*n = receiver address programmed in VISTA control panel

SPECIFICATIONS

Physical:
6-1/4" H x 4-7/8" W x 1" D
(158.75mm x 123.8mm x 25.4mm)
Wiring:
Refer to Wiring Table on page 2
Range:
200' nominal
Frequency:
345 MHz
FOR DETAILS ON THE LIMITATIONS OF THE ENTIRE ALARM SYSTEM, REFER TO THE INSTALLATION INSTRUCTIONS
FOR THE CONTROL PANEL WITH WHICH THIS DEVICE IS USED.
Action
Corrective Action
1.
Replace the battery if the wireless key has a replaceable battery.
2.
Replace the transmitter if the wireless key does not have a replaceable
battery.
Verify that the Data Out wire is connected properly.
Verify that the control panel is not a First Alert-type control panel.
1.
Verify that the Data In wire is connected properly.
2.
Verify the wiring connections between the control and all other devices.
Verify the number of transmitters programmed into the control panel
- 7 -
Alternately flashes "d*" with the device number;
and "--."
Voltage:
12VDC
Current:
Standby 80mA
Backlighting on and
Sounder on 105mA
Relay:
Normally-Open, 1A, 28VDC
Sounder:
Piezo-electric (fire alarm is loud pulsing tone;
burglary/audible panic alarm is two tone
sound
Display

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents