Model 6820 / 6820-EVS Installation Manual
7.
Select the type of device by pressing the up or down arrow key. Refer to Table 9-4 under the column heading
"Type Selection" for a list of choices.
Type
Function
Selection
UNUSED
PHOTO
ION
HEAT
PHOTO DUCT
ACCLIMATE
DETECTOR
HEAT HT
PHOTO-HEAT
BEAM
PHOTO
ION
HEAT
PHOTO DUCT
SUP DET
ACCLIMATE
HEAT HT
PHOTO-HEAT
BEAM
CO ALRM /
FIRE ALRM
CO ALRM /
FIRE SUPR
CO SMOKE
DETECTOR
CO SUPR /
FIRE ALRM
CO SUPR /
FIRE SUPR
Photo
W-DETECTOR
Photo-Heat
Heat
Same as W-
W-SUP-DET
Detector
MANUAL PULL
SWITCH
WATERFLOW
Table 9-4 Point Programming for 6815
Latching Option
Select for SLC points that are unused.
Spot photoelectric detectors.
Spot ionization detector.
Spot heat detector.
Duct photoelectric detector.
Acclimate photoelectric detector.
High temperature heat detector.
Photoelectric detector with heat sensor.
Beam smoke detector.
Latching
Use this option when you want a detector to indicate a supervisory
alarm.
Non Latching
Latching
Detectors programmed as Supervisory can be latching or non-
latching.
Non Latching
Wireless photoelectric detector
Wireless heat detector
Latching
Non Latching
Use this switch type for manual pull stations. This input is always
latched. The switch can clear only when an alarm is reset. This
switch type has the highest fire priority; it overrides any other type of
fire alarm.
Latching
Use this switch type for monitoring water flow in a sprinkler system.
Switch closure will cause a sprinkler alarm. Water flow switches can
be programmed as latching or non-latching.
You can program a delay of up to 90 seconds to be used with a
water flow switch. The delay allows for normal, brief changes in
sprinkler system water pressure. The water flow alarm will not
Non Latching
activate unless the switch is active for the programmed delay time.
If a delay is used, the system begins counting down when the switch
closes. If the switch opens (restores) before the timer expires, a
water flow alarm is not generated. If the water flow switch remains
closed after the timer expires, a water flow alarm will be generated.
9-13
LS10144-001SK-E