5880 Led I/O Module; 5880 Board Layout - Honeywell 6820EVS Installation And Optimization Manual

Addressable fire system emergency voice system
Hide thumbs Also See for 6820EVS:
Table of Contents

Advertisement

LS10144-001SK-E
5.
Press the right arrow to skip over the Enter Module ID and Enter Module name options. A screen similar to
the one shown in Figure 4-34 will display.
6.
Select options for the printer as needed for your installation. Most printers are parallel.
7.
If you are using a serial printer, use the next screen to select serial port options as required for your printer.
Refer to your printer manual if you need more
information.

4.11 5880 LED I/O Module

The 5880 is an LED driver board that can be used in a wide variety of applications, including as an interface with
most customized floor plan annunciator boards. The 5880 can drive up to 40 LEDs and has one PZT controller.
The 5880 also has eight inputs for monitoring dry contacts. When used with the 6820EVS the 5880 inputs can be
programmed to replicate the eight EVS buttons located on the front of the voice control module. (See section 9.5
for programming options). Up to 8 5880s can be added to the 6820/EVS system.
The following sub-sections describe hardware installation. Refer to Section 9 for programming information.
4.11.1

5880 Board Layout

Figure 4-35 shows the locations of screw terminals for connection to the panel and contact monitor wiring; pin
Figure 4-34 Selecting Printer and Output Port Options
Option
Baud Rate:
Data Bits:
Stop Bits:
Parity:
Select type of printer
Parallel or Serial
Defaulted to no
Select "Yes" for event logging
Choices
75 - 19200
5 - 8
.5, 1, 2
None, Even, Odd
4-26
Control Panel Installation

Advertisement

Table of Contents
loading

This manual is also suitable for:

6820

Table of Contents