Voice Options; Edit Timers; Control Lockout; Auto Reset Evs Mic Triggered Event - Honeywell 6820EVS Installation And Optimization Manual

Addressable fire system emergency voice system
Hide thumbs Also See for 6820EVS:
Table of Contents

Advertisement

LS10144-001SK-E
5.
Press * to add rows, Press ENTER to edit data
6.3

Voice Options

6.3.1

Edit Timers

1.
Enter the installer code. The panel will automatically go to the main menu.
2.
Select 6 for Network Programming.
3.
Select 7 for Voice Options.
4.
Choose Site.
5.
Select 1 for Edit Timers

6.3.1.1 Control Lockout

The Control Lockout countdown timer is set to the programmed value when an LOC gains EVS Control. The
timer starts over upon any key press at the EVS Control LOC. While the Control Lockout timer is active, an LOC
of equal priority must request EVS control. The Control Lockout timer is cleared when EVS Control is
relinquished. The Control Lockout timer does not apply to EVS Super User control.
Select Immediate/Timer/Never
Range 0-720 min/0-59 sec

6.3.1.2 Auto Reset EVS MIC Triggered Event

If the Timer is selected, the event will automatically reset after being active for the programmed time. If Event
Disabled is selected, the event will not be allowed to be activate from an LOC Station. Selecting Never will
require an emergency system reset to be performed to reset the event.
Select Never/Timer/Event Disabled, Range from 1-240 min
Figure 6-1 Communicator Reporting (4x20 screen)
6-6
Network Management

Advertisement

Table of Contents
loading

This manual is also suitable for:

6820

Table of Contents