Edit Banner; Slc Family; Jumpstart® Autoprogramming - Honeywell 6820EVS Installation And Optimization Manual

Addressable fire system emergency voice system
Hide thumbs Also See for 6820EVS:
Table of Contents

Advertisement

Model 6820 / 6820-EVS Installation Manual
9.
Press the up or down arrow to select the month (January – December) Daylight Saving Time ends, then press
ENTER two times to make your selection and exit.
9.6.5

Edit Banner

The banner is the message that displays on the panel LCD when the system is normal, that is, when no alarms or
troubles exist and the system menus are not in use. A custom message of up to 40 characters can be created.
If a customize message is not created, the system will use the internal banner. You cannot change the internal
banner.
To customize the banner display message:
1.
Enter the installer code. The panel will automatically go to the main menu.
2.
Select 7 for Program Menu.
3.
Select 5 for System Options.
4.
Select 7 for Edit Banner. A screen similar to the one shown in 5. will display.
Note: See Appendix B for instructions on how to edit the banner.
5.
Select each letter by pressing the up or down arrow, then press the right arrow to move to the next character.
6.
When done, press ENTER to move to line two of the custom banner.
9.6.6

SLC Family

The 6820/6820EVS supports SD protocol SLC devices or SK protocol SLC devices. You must configure the
6820/6820EVS to accept the protocol of the devices you are installing. You cannot mix SLC devices of different
protocols.
Note: You cannot mix SK and SD protocol SLC devices on the same panel.
1.
Enter the installer code. The panel will automatically go to the main menu.
2.
Select 7 for Program Menu.
3.
Select 5 for System Options.
4.
Press 8 for SLC Family.
5.
Press Up arrow to select the desired SLC device type.
6.
Press ENTER to accept the displayed SLC device type.
Note: When changing SLC type from one protocol to another, the following message will appear:
Note: Message when changing SLC family from SK to SD: Changing to this SLC family will remove all external
6815's
Note: Message when changing from SD to SK: SLC family will remove all 5815XL's on the system
9.7
JumpStart
Panels support an incremental JumpStart.
Figure 9-11 SLC family change
®
AutoProgramming
®
For Example: After initial JumpStart
9-25
LS10144-001SK-E
®
& customization, if you add