Model 6820 / 6820-EVS Installation Manual
Section 12
Reporting
This section lists receivers that are compatible with this control panel, and the reporting codes sent by the control
panel for SIA and Contact ID formats.
12.1 Receivers Compatible with the Control Panel
Table 12-1 shows receivers compatible with the control panel.
Table 12-1: Receivers Compatible with the Control Panel
Manufacturer
Honeywell
Honeywell Security
Ademco
Ademco
Sur-Gard
Osborne Hoffman
Event Description
System Events
AC power low trouble
AC power low trouble restore
Auto dialer test communications
trouble line 1
Auto dialer test communications
trouble line 1 restore
Auto dialer test communications
trouble line 2
Auto dialer test communications
trouble line 2 restore
Automatic test normal
Model
Model 9800
Model 9000 (SIA formats)
AlarmNet 7810-ir
MX8000
Model 685 (Contact ID )
SG-MLR2-DG (V. 1.64 or higher)
Quickalert
Table 12-2: Reporting Formats Table
SIA Reporting Format
SIA pi Modifier
Module
SIA
Parameter Fixed Length
ID # (If
Event
Any)
Codes
Note: System Events are reported when either "Report by Point" or
Report by Zone is selected
AT
0
AR
0
YC
1
YK
1
YC
2
YK
2
RP
0
12-1
Format
SIA and Contact ID
SIA
IP and Cellular Receiver,
Contact ID only
SIA and Contact ID
Contact ID
SIA and Contact ID
SIA and Contact ID
Contact ID Reporting Format
SIA
Qualifier
Format NN -
panel ID
XX- SBUS ID
ZZZ- Zone #
PPPP- Point #
GGG- Group #
E- Emergency #
RRRR-Receiver #
ATNN000000
1
ARNN000000
3
YCNN000001
1
YKNN000001
3
YCNN000002
1
YKNN000002
3
RPNN000000
1
LS10144-001SK-E
Event
Group #
Contact #
Code
301
00
000
301
00
000
350
Receiver # 001
350
Receiver # 001
350
Receiver # 002
350
Receiver # 002
602
00
000